Grounding portable PZ-1000 (hereinafter referred to as grounding)
designed to protect service personnel from injury
electric current during work in the disconnected area
PL, in the event of an unforeseen occurrence in this area of high
or applied voltage.
Grounding is intended for operation in climatic
Conditions In category 1 according to GOST-15150.
MAIN TECHNICAL CHARACTERISTICS:
The nominal voltage of electrical installations is 1 kV
The length of the bar with the clamp is not less than 320 mm
The number of clamps is 5 pcs.
Number of bars - 5 pcs.
The length of the insulating part of the rod is at least 70 mm
The length of the bar handle is at least 150 mm.
The length of the grounding wire is 9000 mm
The length of the wire between the phase clamps is 900 mm
The cross-section of the grounding wire is 16 mm²
Thermal resistance current for 3 s – 2.5 kA
The mass of the grounding, no more than 4.35 kg
Grounding is made in accordance with the requirements of TU-1014-13420264-11-95 and GOST R51853
Відгуки
Відгуків немає, поки що.