2. TECHNICAL CHARACTERISTICS
2.1. Operating voltage range, kW from 2.2 to 10
2.2. Indicator ignition threshold, V not higher than 550
2.3. The indicator is single-channel, single-functional
2.4. Service life without replacing the battery, years, not less than -10
2.5. Weight of the indicator, kg not more than 0.4
2.6. Overall dimensions, mm 50x600
2.7. The length of the insulating part, mm 260x10
2.8. The length of the handle, mm 120
3. COMPLETENESS
3.1. Indicator of high voltage type__ 1pc.
3.2. Case_____________________________1 pc.
3.3. Passport ___________________________1 copy.
3.4. Test protocol________________ 1 copy.
4. DEVICE AND PRINCIPLE OF WORK
4.1. The indicator consists of a working part, an insulating part and a handle
4.2. An indicator is built into the working part of the pointer.
5. INSTRUCTIONS OF THE SECURITY MAYOR
5.1. The design of the pointer meets the requirements of the "Rules of application and testing of protective equipment used in electrical installations".
5.2. The handle of the indicator has a ring-shaped stop on the side of the insulating part, the height of which is not less than 5 mm.
5.3. The indicator works without grounding any of its parts in all electrical installations, except overhead lines.
6. PREPARATION OF WORK INDEX AND WORK PROCEDURES
6.1. Remove the contents from the case and check for completeness.
6.2. Unscrew the working part of the pointer, screw it into the insulating part.
6.3. Make a visual control of the pointer and let it go to work.
7. MANUFACTURER'S WARRANTIES
7.1. The manufacturer guarantees compliance of the pointer with the requirements of GOST 20493-90 and TU RA 01802164.0668-97, provided that the user complies with the conditions of operation, storage and transportation.
7.2. The warranty period of operation is established for 2 years from the day of commissioning.
7.3 The manufacturer is responsible for hidden defects of the pointer during its service life.
7.4. The warranty period of storage is 6 months from the moment of production of the directory.
TEST RESULTS
The pointer withstood the test with a voltage of 12 kW for 1 minute.
The insulating part of the pointer withstood the test with a voltage of 40 kW for 5 minutes.
The indicator ignition threshold voltage is no more than 550V.
Conclusion: The voltage indicator is suitable for use in installations with a voltage from 2.2 to 10 kW.
Reviews